Home
Product Catalog
News
Contact Us

Product Catalog 

GST Conventional Reflective Beam Smoke Detector

Model No.︰JTY-HF-GST102
Brand Name︰GST
Country of Origin︰China
Minimum Order︰6 pc
Share on:

 Total 18 Related Items 
Prev12345Next

Product Description

1 Features

JTY-HF-GST102 type beam smoke detector fire reflective type linear non-coding sense infrared beam smoke detector . Detectors must be supporting the use of reflectors , but requires the use of a reflector or four different decisions based on the distance between the two installed . Detector has the following characteristics :

( 1 ) The transmitter , receiver into one, easy to install, easy to use, optical collimation is good ;

( 2 ) with automatic calibration function , ensure the completion of commissioning by a single person in a short , simple operation, easy ;

( 3 ) has a self- diagnostic function , the detector can monitor internal fault ;

( 4 ) with automatic compensation function, for a certain degree of dust contamination , and the position offset of the launch tube causes the received signal is reduced aging factor can be automatically compensated ;

( 5 ) Field set three levels of sensitivity for different levels of dust place ;

( 6 ) has a fire , failure of passive output contacts ;

( 7 ) to detect optical design clever , strong anti-jamming performance ;

( 8 ) sealed design with waterproof performance ;

( 9 ) patented product , patent No. ZL 033580537.

4.9.2 The main technical indicators

( 1 ) Power supply voltage : DC15V ~ DC28V

( 2 ) Supply Current:

Debugging current ≤ 20mA

Monitor current ≤ 12mA

Alarm current ≤ 22mA

( 3 ) the sensitivity level

A : 1.3 ± 0.3dB

Two : 1.7 ± 0.3dB

Three : 2.3 ± 0.3dB

( 4 ) Indicator :

Commissioning Status: green and yellow lights lit in a particular way or shiny

Normal monitoring state : red LED flashes periodically

Fire Status: Steady red light , yellow light goes out

Fault Status : yellow indicator light

All optical path is blocked : first reported the fault detector and light yellow light , 20s after the probe and reported to the fire and lit the red light , yellow light goes out

( 5 ) Protection area:

Detectors maximum protection area 14 × 100 = 1400m2, maximum width of 14m

( 6 ) Use of the environment :

Temperature : -10  C ~ +55  C

Relative humidity ≤ 95%, non-condensing

( 7 ) Dimensions:

Length : 206mm Width : 95mm Thickness : 95mm

4.9.3 structural characteristics , installation and wiring

The structure and shape of the detector and reflector installation option to install and JTY-HM-GST102 type beam smoke detector fire the same .

On-site installation , you need to 24V DC power cord ( non-polar ) , connected to the detector terminals D1, D2; terminals K21, K22 fault passive output normally open contacts , terminals K11, K12 was no fire source output normally open contact ; reflector without wiring. Terminals shown in Figure 1 - 31.

Figure 1 - 31

Wiring requirements : Connecting K11, K12, K21, K22 twisted pair signal lines using fire-retardant , cross-sectional area ≥ 1.0mm2; power lines D1, D2 BV flame retardant cable, cross-sectional area ≥ 1.5mm2.

Product Image


Related Products
Tanda Reflective Laser Beam Smoke Detector
Tanda Reflective Laser Beam Smoke Detector
Universal safety lock cable laptop lock with keys
Universal safety lock cable laptop lock with keys
 Reflective gst Infrared Beam Smoke Detector
Reflective gst Infrared Beam Smoke Detector
Smoke Detector With Network Signal Output
Smoke Detector With Network Signal Output




Home  |  Product Catalog  |  News  |  Contact Us  |  Sitemap  |  Mobile Version

Powered by DIYTrade.com  Build your FREE website !